A pair of T-105s in series has the same amperage, and as a result,
amp-hours, as a single T-105, 225AH at a 20-hour rate, which is
11.25A. All you do by putting them in a series pair is double the
voltage. As long as you don't exceed that discharge rate (with a
light or two), you can count on that many AHs.
T-105s can be discharged down to 20%, but they'll last 3 times longer
(i.e. have 3 times the number of discharge cycles) if you keep that
to 50%. If you do that, a pair of T-105s in series will run the 5.5A
furnace continously for about 21 hours before the batteries are down
to 50% of their capacity.
--